EasyManua.ls Logo

Fuji Electric FRENIC-VG Series - Communication Error Measures

Fuji Electric FRENIC-VG Series
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-18
5.1.10 Communication error measures
When executing run commands or applying command data via RS-485, it is possible to continue
running the inverter without tripping the alarm, even if there is a transmission error, by
implementing the following measures. The following examples show communication alarms
(keypad displays er5 ) generated when operating the inverter from the master side.
(a) H32 = 0; Forced stop (Forced stop: idling stop during alarm)
(b) H32 = 1; Idling stop after set time elapses following transmission error
(Operation stops after continuing for timer set time, H33: timer time = 5.00 s)
(c) H32 = 2; Operation continues if cause of transmission error is resolved within timer time set in
(b) above.
(Operation stops after error continues beyond timer set time, H33: timer time = 5.00 s)
(d) H32 = 3; Operation continues even after transmission error occurs (continued operation).
Transmission status
Keypad display
Run command
Speed setting
Normal Er5
Error reset
OO
Good
Good
Error
伝送
KEYPAD表
運転
速度
Normal Er5
Error reset
ON ON
Good Good
Error
5.0(s)
Transmission status
Keypad display
Run command
Speed setting
伝送
KEYPAD
運転
速度
Normal
ON
Good Good
Error
5.00(s)
Transmission status
Keypad display
Run command
Speed setting
伝送
KEYPAD表示
運転
速度
Normal
ON
Good Good
Error
5.00(s)
Transmission status
Keypad display
Run command
Speed setting

Table of Contents

Related product manuals