6.7.9.3 Monitor code/command code (o32 = 1 to 4)
Table 6.7.24 Monitor Code List (With o32 = 1 to 4)
Code No. Monitor item Unit Remarks
00
H
RWr0, RWr4-7: No monitoring (Fixed to 0)
RWr1: Motor speed
01
H
Output frequency 0.01 Hz
02
H
Output current 0.01 A/0.1 A
Rating of less than 75 kW: Unit
of 0.01
Rating of 75 kW or more: Unit of
0.1
03
H
Output voltage 0.1 V
05
H
Speed setting 1 r/min
06
H
Rotating speed 1 r/min
07
H
Calculated torque 0.1%
08
H
DC link bus voltage 0.1 V
09
H
|
0A
H
No monitoring (Fixed to 0)
0B
H
Output current peak value 0.01 A/0.1 A
0D
H
Power consumption (input power) 0.01 kW/0.1 kW
0E
H
Motor output 0.01 kW/0.1 kW
Rating of less than 75 kW: Unit
of 0.01
Rating of 75 kW or more: Unit of
0.1
0F
H
Operation command
10
H
Output terminate status
11
H
Motor load (torque current) 0.1%
12H Flux command 0.01%
13H Position pulse 1 pulse
14H Cumulative power-ON time 1 hr
15H
|
16H
No monitoring (Fixed to 0)
17H Cumulative motor 1 run time 1 hr
18H Motor load factor 0.1%
19H Input watt-hour 1 kWhr
20H Torque command 0.1%
21H Torque current command 0.1%
22H Motor output 0.01 kW/0.1 kW
Rating of less than 75 kW: Unit
of 0.01
Rating of 75 kW or more: Unit of
0.1
23H
|
33H
No monitoring (Fixed to 0)
34H PID command value 0.1%
35H PID feedback 0.1%
36H PID deviation 0.1%
Detailed description on operation command
b15 b8 b7 b0
RST X14 X13 X12 X11 X9 X8 X7 X6 X5 X4 X3 X2 X1 REV FWD
Figure 6.7.17
Detailed description on output terminate status
b15 b8 b7 b0
Y18 Y17 Y16 Y15 Y14 Y13 Y12 Y11 - - - Y5A Y4 Y3 Y2 Y1
- : Empty (Fixed to 0)
Figure 6.7.18