6.7 CC-Link Interface Card
6-177
Chap. 6
CONTROL OPTIONS
Table 6.7.25 Command Code List (With o32 = 1 to 4)
Item Code number Description Remarks
Reading of function code 0000
H
to FF63
H
Reads or writes data from/to
inverter's function codes.
Inverter's function codes should be specified
in the format shown in Table 6.7.27.
Writing of function code 0080
H
to FFE3
H
Writes data into inverter's function
codes.
Data cannot be written into function code
H01 or P02.
Reading of operation
mode
007B
H
0000
H
: Link operation (CC-Link)
0001
H
: Terminal command for
external drive
0002
H
: Keypad operation
0003
H
: Others
0000
H
: ([LE]=ON, H300, and remote
mode)
0001
H
: ([LE]=OFF or H30=0), F02=1, and
remote mode
0002
H
: (([LE]=OFF or H30=0) and F02=0)
or local mode
0003
H
: Others
Writing of operation
mode
(Note 2)
00FB
H
0000
H
: Link operation (CC-Link)
0001
H
: Terminal command for
external drive
0002
H
: Keypad operation
0000
H
: Writing of H30=3, [LE]=ON (Note 1)
0001
H
: Writing of H30=0, F02=1
0002
H
: Writing of H30=0,F02=1,F01=0
Alarm code
Reading of latest and last
codes
0074
H
Alarm content Reading of latest
and last codes.
Lower byte: Latest alarm code
Higher byte: Last alarm code
Alarm code
Reading of 2nd last and
3rd last codes
0075
H
Alarm content Reading of 2nd last
and 3rd last codes.
Lower byte: 2nd last alarm code
Higher byte: 3rd last alarm code
Alarm code
Reading of 4th last and
5th last codes
0076
H
Alarm content Reading of 4th last
and 5th last codes.
Lower byte: 4th last alarm code
Higher byte: 5th last alarm code
Alarm code
Reading of 6th last and
7th last codes
0077
H
Alarm content Reading of 6th last
and 7th last codes.
Lower byte: 6th last alarm code
Higher byte: 7th last alarm code
Reading of speed
command
006D
H
Reads out the speed command
value. (Monitoring of frequency set
via CC-Link)
Writing of speed
command
00ED
H
Write speed command
The allowable setting range is from 0 to
+/-20000. Specify the ratio of the frequency
relative to the maximum frequency (defined
by F03 in Hz) being assumed as 20000.
Clear
alarm history
00F4
H
9696
H
: Clears alarm history.
Function code
initialization
00FC
H
9696
H
: H03=1
Inverter
reset
00FD
H
9696
H
: Clear alarm
(Note 1) Assignment of [LE] to terminal X gives priority to [LE] via terminal X.
(Note 2) In local mode, running mode cannot be changed.
Table 6.7.26 Response Code List (With o32 = 1 to 4)
Code number Item Description
00
H
Normal (No error) Command code execution normally completed
01
H
Write mode error ・Function code was written while the inverter was running
・Function code was written while E2PROM was being written.
・Function code was written at the time of transmission error.
・S code was written when upper link (loader etc.) was enabled.
・Function code was written in a mode where edition is not permitted.
02
H
Function code selection error ・Accessed to a nonexistent function code
・Data was written to a read only function code.
03
H
Out of setting range Set data is out of changeable range.