6-84
U60 U-Ai/pulse data monitor selection
Select whether the function codes U61 - U63 can monitor the U-Ai (universal Ai) or pulse data. U64 is
excluded from pulse data monitoring.
The default value is U60=0 and the U-Ai function is not selected, and U61 to U64 all act as the user
function codes. When U61 to U64 are set for monitoring (rather than as the user function codes), do not
write data to them.
1 When U60=0
U-Ai function is
selected
U61 U62 U63 U64
Not selected User function code User function code User function code User function code
Selected U-Ai1 monitor U-Ai2 monitor U-Ai3 monitor U-Ai4 monitor
2 When U60=1
U-Ai function is
selected
U61 U62 U63 U64
Not selected User function code
Selected
Pulse train position
command (PG(PR)
input) monitor
Position detection
(internal or PG(PD)
input) monitor
Position detection
(PG(PD) Z-phase
input) monitor
U-Ai4 monitor
When the U-Ai function is selected, the universal Ai (U-AI) is selected with Ai function selection
(E49-E52).
U-Ai3 and U-Ai4 are only valid when OPC-VG1-AIO or OPC-VG1-AI is installed.