6-150 
  Setting value of function code  Remarks 
Condition: No. of INVs  1 unit  2 units  3 units 
No. of inverters connected to   
one unit of motor 
Exciting current/ 
magnetic Flux 
weakening current (-Id) 
P08  240.3  120.2  80.10 
x (1/No. of units participating in direct 
parallel connection) 
Torque current  P09  508.1  254.1  169.4 
x (1/No. of units participating in direct 
parallel connection) 
Slip frequency (driving)  P10  0.274  0.274  0.274   
Slip frequency (braking)  P11  0.274  0.274  0.274   
1 P12 3.00  3.00  3.00   
2 P13 0.00  0.00  0.00   
Iron loss 
factor 
3 P14 0.00  0.00  0.00   
1 P15 89.3  89.3  89.3   
2 P16 83.3  83.3  83.3   
3 P17 71.4  71.4  71.4   
4 P18 59.5  59.5  59.5   
Magnetic 
saturation 
factor 
5 P19 47.6  47.6  47.6   
Secondary time constant  P20  1.122  1.122  1.122   
Induced voltage factor  P21  350  350  350   
1 P22 1.000  1.000  1.000   
2 P23 1.000  1.000  1.000   
R2 
correction 
factor 
3 P24 1.000  1.000  1.000   
Exciting current 
correction factor 
P25 0.000  0.000  0.000   
P-gain  P26 1.0  0.5  0.5 
ACR 
Constant 
I-time P27 1.0  5  5 
Use these setting values as initial setting, 
and change them later. 
*  Adjustment parameters (Change the 
setting while checking operation in test 
runs.) 
Pulse resolution  P28  1024  1024  1024   
Thermistor selection  P30  1  1  1   
 
 
1) As a representative inverter, first motor codes are indicated. The same setting values apply to
the second and third inverters when set/selected, too. 
2) Setting values of P03, 04, 08, 09 become floating points. Set the values by calculating the
to settable decimal point. 
  Set the values by rounding them when they cannot be divided. 
3) Set ACR constant to the setting values specified in this Table for test runs. Then, change the
values after checking operation conditions.