6.7  CC-Link Interface Card 
6-163 
Chap. 6 
CONTROL OPTIONS 
Note 2:  In case of light alarm (o30=0/1), resetting can be performed unless alarm cause has been removed completely. In case of 
the light alarm (o30=2) or heavy alarm, however, resetting cannot be done until the cause has completely been removed. 
Note 3:  With o30=1, 2, or 3: For deceleration to stop, the motor stops with the time of deceleration (F08, C47, C57, or C67) 
specified at that time. 
With o30=2: For restart, the motor accelerates in the acceleration time (F07, C46, C56, or C66) specified at that time. 
Note 4:  With o30=2, if an error in communications circuit is removed during deceleration, the motor reaccelerates at that time. 
Note 5:  Communications error codes for light alarm/heavy alarm can be confirmed on the communications status screen for 
maintenance information of the keypad. 
 
 
 
 
 
 
Figure 6.7.8  Communication Error Codes 
NRK=××××× 
NRR=×××××    ×× 
NRO=×××××    ×× 
NRL=×××××    ×× 
∧∨ÆPAGE  SHIFT  4
-: Without error 
2: Light alarm (CC-Link error) 
3: Heavy alarm (Option error)