6.7 CC-Link Interface Card
6-163
Chap. 6
CONTROL OPTIONS
Note 2: In case of light alarm (o30=0/1), resetting can be performed unless alarm cause has been removed completely. In case of
the light alarm (o30=2) or heavy alarm, however, resetting cannot be done until the cause has completely been removed.
Note 3: With o30=1, 2, or 3: For deceleration to stop, the motor stops with the time of deceleration (F08, C47, C57, or C67)
specified at that time.
With o30=2: For restart, the motor accelerates in the acceleration time (F07, C46, C56, or C66) specified at that time.
Note 4: With o30=2, if an error in communications circuit is removed during deceleration, the motor reaccelerates at that time.
Note 5: Communications error codes for light alarm/heavy alarm can be confirmed on the communications status screen for
maintenance information of the keypad.
Figure 6.7.8 Communication Error Codes
NRK=×××××
NRR=××××× ××
NRO=××××× ××
NRL=××××× ××
∧∨ÆPAGE SHIFT
-: Without error
2: Light alarm (CC-Link error)
3: Heavy alarm (Option error)

Table of Contents