6.7 CC-Link Interface Card
6-169
Chap. 6
CONTROL OPTIONS
Table 6.7.14 Remote Input Signal in VG7 Compatible Mode (FRENIC-VG -> Master)
Device No. Signal name Description
RXn0 Running forward OFF: Except running in forward direction (Stopped or Rotating in reverse direction)
ON: Rotating in forward direction
RXn1 Running reverse OFF: Except running in reverse direction (Stopped or Rotating in forward direction)
ON: Rotating in reverse direction
RXn2 Terminal Y1
function
With speed. Turned ON with (N-EX)
RXn3 Terminal Y2
function
Speed match. Turned ON with (N-AG1).
RXn4 Terminal Y3
function
Arrival at speed. Turned ON with (N-AR).
RXn5 Terminal Y4
function
Speed detection 1. Turned ON with (N-DT1)
RXn6 Terminal Y5
function
Operation preparation completed. Turned ON with (RDY).
RXn7 Alarm relay output Inverter's protection function is operated, and the signal is turned
ON when output stops.
Functions to be provided
by factory default are
shown at left. Setting
terminal Y function can
change output contents.
RXn8
|
RXnB
Not used. -
RXnC Monitoring The "Monitoring" signal (RXnC) is turned ON when turning the "Monitor command" (RYnC)
ON specifies a monitored value for remote register RWrn (refer to Table 6.7.16). Turning the
"Monitor command" (RYnC) OFF turns this signal OFF.
RXnD Speed setting
completed (RAM)
This signal is turned ON when turning the "Speed setting command" signal (RYnD) ON
writes a speed command into the inverter's volatile memory (RAM). Turning the "Speed
setting command" signal (RYnD) OFF turns the "Speed setting completed" signal (RXnD)
OFF.
RXnE Not used. -
RXnF Command code
execution
completed
This signal is turned ON when turning the "Command code execution request" (RYnF) ON
has completed the execution of processing corresponding to the command code (RWwn+2).
Turning the "Command code execution request" (RYnF) OFF turns the "Command code
execution completed" signal (RXnF) OFF.
RX(n+1)0
|
RX(n+1)9
Not used. -
RX(n+1)A Alarm state flag This signal is turned ON when an inverter alarm (alarm other than
er3
) is generated.
RX(n+1)B Remote station
ready
This signal is turned ON when completing initial data setting places the inverter in the ready
status after the inverter has been powered ON or the hardware has been reset. (This signal is
used for interlocking with reading or writing from/to the master unit.) This signal is turned
OFF concurrently when the "Alarm state flag" (RX(n+1)A) is turned ON if the inverter alarm
is generated.
RX(n+1)C
|
RX(n+1)F
Not used. -
n: Value determined by a station address
Note 1: When the condition setting switch of the master unit for "Input data status of data link error station (SW4)" is set to ON,
input data from the data link error station is retained in the status just before the occurrence of the error. Note that this
remains signals, e.g., remote station ready, etc., ON even if an inverter alarm is generated.
Note 2: If an operation command is output from the master when the instruction via communications is disabled (H30=0, 1, or [LE]
instruction OFF), the inverter does not run. However, the input signals "Speed setting completed" and "Command code
execution completed" signal are turned ON. Care must be taken for this. In addition, "I/O check" can be performed on the
keypad to confirm whether input signal is issued from the link (COM), even if the command via communications is
disabled.