6.7 CC-Link Interface Card
6-181
Chap. 6
CONTROL OPTIONS
Table 6.7.31 Remote Register in 4 X Mode (FRENIC-VG->Master)
Address Signal name Description Remarks
RWrn+0 Monitored value 1 When RYnC is turned ON, the monitored value specified with
monitor code 1 is output.
RWrn+1 Monitored value 2 When RYnC is turned ON, the monitored value specified with
monitor code 2 is output.
RWrn+2 Response code Response codes corresponding to RWwn+2 command code (refer
to Table 6.7.26) are set. For normal response, "0" is set. If data is
incorrect, the codes are set to a value other than "0".
RWrn+3 Read data If the command code has normally been executed, the response
data for that command (specified by the command code) is
automatically written.
RWrn+4 Monitored value 3
RWrn+5 Monitored value 4
RWrn+6 Monitored value 5
RWrn+7 Monitored value 6
Outputs data of the monitor items specified with monitor codes 3
to 6 when RYnC is ON.
RWrn+8 Alarm code The content of the alarm code specified in RWwn+8 is
automatically written into the lower 8 bits of RWrn+8. The upper
8 bits of RWwn+8 will be echoed back into the upper 8 bits of
RWrn+8.
For the alarm code, refer to
Chapter 4, Section 4.2.4.2,
Type [14].
RWrn+9 Motor speed at the
time of latest
alarm
The motor speed with the alarm, specified with RWwn+8,
generated is stored. For alarms other than the latest one, response
is given with "0".
0 to ±20000
(Nmax with ±20000)
Supported only for the latest
alarm.
RWrn+A Output current at
the time of latest
alarm.
This register stores the output current applied at the occurrence
time of the alarm specified in RWwn+8. "0" is written except for
the latest alarm.
Rating of less than 75 kW:
Unit of 0.01 A
Rating of 75 kW or more:
Unit of 0.1 A
RWrn+B Output voltage at
the time of latest
alarm.
This register stores the output voltage applied at the occurrence
time of the alarm specified in RWwn+8. "0" is written except for
the latest alarm.
Unit of 0.1 V. "0" except for
the latest alarm.
RWrn+C Cumulative
power-ON time at
the latest alarm
occurrence
This register stores the cumulative power-ON time elapsed until
the occurrence time of the alarm specified in RWwn+8. "0" is
written except for the latest alarm.
Unit: 1 h
RWrn+D
|
RWrn+F
Not used. -
n: Value determined by a station address