6-230
(3) Output circuit
The output interface block allows bi-directional power connections. The CME is common to all contacts
(Y11 to Y30). Therefore, no bi-directional signals can coexist.
CME
Power supply voltage: 28 V max.
Continuous current: 50 mA max.
Y11
CEM is isolated from CM.
CME
Power supply voltage: 28 V max.
Continuous current: 50 mA max.
Y11
CEM is isolated from CM.
Figure 6.12.5
As shown in Figure 6.12.5, connect a surge-absorbing diode to both ends of the excitation coil when
connecting the control relay.
Table 6.12.3 Software Specifications
Item Specification
Read
cycle
Data is read at 1-ms cycles and determined if the data consecutively read twice
coincides.
Input data
Function
allocation
Possible if DIOA is used. See table 6.12.6.
Refresh
cycle
Refreshed at 1-ms cycles.
Some output functions may be refreshed at cycles longer than 1 ms.
Output data
Function
allocation
Possible if DIOA is used. See table 6.12.7.