6-230 
(3) Output circuit 
The output interface block allows bi-directional power connections. The CME is common to all contacts 
(Y11 to Y30). Therefore, no bi-directional signals can coexist. 
CME
Power supply voltage: 28 V max.
Continuous current: 50 mA max.
Y11
CEM is isolated from CM.
CME
Power supply voltage: 28 V max.
Continuous current: 50 mA max.
Y11
CEM is isolated from CM.
 
Figure 6.12.5 
As shown in Figure 6.12.5, connect a surge-absorbing diode to both ends of the excitation coil when 
connecting the control relay. 
Table 6.12.3  Software Specifications 
Item Specification 
Read 
cycle 
Data is read at 1-ms cycles and determined if the data consecutively read twice 
coincides. 
Input data 
Function 
allocation 
Possible if DIOA is used. See table 6.12.6. 
Refresh 
cycle 
Refreshed at 1-ms cycles. 
Some output functions may be refreshed at cycles longer than 1 ms. 
Output data 
Function 
allocation 
Possible if DIOA is used. See table 6.12.7.