6.15 E-SX Bus Interface Card
6-251
Chap. 6
CONTROL OPTIONS
(2) Status display LED RUN, ERR
The status of the local station (running/error) is indicated by the RUN/ERR LED on the option board.
The option determines the status of the local station, which is a slave station, and thus this may differ
from the RUN/ALM status displayed on the MICREX-SX CPU.
Table 6.15.2 LED Display
Status of slave RUN (green) ERR (red)
Initial E-SX bus transmission not received OFF OFF
E-SX bus transmission received Flashing OFF
Normal ON OFF
Option hardware error OFF ON Heavy alarm
Master down detected ON ON
Light alarm ON ON
Local station setting error (does not match master or
station address outside range)
Communication error detected (missed reception 3
tacts in succession)
Other inverter alarm occurred
Inverter power OFF
(including bypass operation)
OFF OFF
Table 6.15.3 Software Specifications
Item Specifications
Data update cycle (*1) Minimum 250 s
Run command Run forward and reverse commands, alarm reset command, X1 to X14 commands
Speed/torque
command
1-word data
Bit data of running, braking, torque limiting, alarm relay and other signals
Oper
ation
Operation status
output
Return speed (1 word), torque output (1 word), current return position (2 words)
(supported in near future)
Option function codes o30, o31, U11 to U13
Protective functions
er4
: Network error (E-SX bus error) (*2)
*Light alarm:
er4
alarm action can be set with o30, o31.
*Heavy alarm: Immediate
er4
alarm.
arf
: Toggle error (*3)
The 2-bit signals sent by the PLC, toggle signal 1 TGL1 and toggle signal 2
TGL2, are monitored, and this error occurs if the specified change pattern is
not received before the time set in H144 elapses.
are
: E-SX bus tact synchronization error (*4)
Occurs when synchronization of the E-SX tact cycle and inverter control cycle is
lost due to noise or other factors.
*1 The data update cycle depends on the carrier frequency setting, E-SX bus tact cycle of the MICREX-SX, and
task cycle of the application program.
*2 For light and heavy alarms, refer to "6.15.6 Protective
operations".
*3 For details on toggle signals and toggle errors, refer to "TGL1" and "TGL2" in the explanation of E01 to E13 in
Chapter 4, Section 4.3 "Details of Function Codes." The toggle pattern for ON/OFF of TGL1 and TGL2 must
be created in the MICREX-SX program.
*4 For E-SX bus tact synchronization errors (
are
), refer to Section 6.15.10 "Synchronization of E-SX bus tact
cycle and inverter control cycle
."