EasyManua.ls Logo

Fuji Electric FRENIC-VG Series - Page 45

Fuji Electric FRENIC-VG Series
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 Fuji General-purpose Communications
5-25
Chap. 5 USING STANDARD RS-485
Polling request frame [Host J Inverter]
0 1 2 3 4 5 6 7
SOH
Station No.
ENQ
Command
ETX BCC
1 2 1 1 1 2
(byte)
Va lu e s
Byte Field
ASCII format Hexadecimal format
Description
0 SOH SOH 01
H
Transmission begins
1 '0' - '3', '9' 30
H
- 33
H
, 39
H
Inverter station address (Decimal: tens place)
2
Station No.
'0' - '9' 30
H
- 39
H
Inverter station address (Decimal: ones place)
3 ENQ ENQ 05
H
Transmission request
Request command
'g' 67
H
Speed detection value (M06)
'h' 68
H
Torque command monitor (M07)
'i' 69
H
Torque current monitor (M08)
'j' 6A
H
Output frequency monitor (M09)
4 Command
'k' 6B
H
Run status monitor (M14)
5 ETX ETX 03
H
Transmission ends
6 '0' - '9', 'A' - 'F' 30
H
- 39
H
, 41
H
- 46
H
Sum-check 1 (Hexadecimal: tens place)
7
BCC
'0' - '9', 'A' - 'F' 30
H
- 39
H
, 41
H
- 46
H
Sum-check 2 (Hexadecimal: ones place)
BCC target

Table of Contents