5.4 FRENIC-VG Loader
5-49
Chap. 5 USING STANDARD RS-485
Trace specifications
Item Traceback Real-time trace Historical trace
Sampling time
Detected current value,
angle of current flow
50 μs to 83.36 μs
100 μs to 166.72 μs
Other than those above
400 μs to 666.88 μs
1 ms to 1s
1 ms to 1s
Detected current value,
angle of current flow
50 μs to 83.36 μs
100 μs to 166.72 μs
Other than those above
400 μs to 666.88 μs
1 ms to 1 s
Number of
sampling points
1100 point/Ch
Before trigger: 1000 points/Ch
After trigger: 100 points/Ch
15000 points/Ch
(Number of points that can
be displayed sequentially)
5456 to 24549 points/Ch
(This number increases or
decreases depending on the
number of channels.)
Display data size
Analog: 8 channels
Digital: 16 channels
Analog: 8 channels
Digital: 16 channels
Analog: 8 channels
Digital: 16 channels
Selected data size
Analog: 26 items
Digital
IN: 16 items
OUT: 16 items x 8 blocks
Analog: 26 items
Digital
IN: 16 items x 6 blocks
OUT: 16 items x 6 blocks
Analog: 26 items
Digital
IN: 16 items x 6 blocks
OUT: 16 items x 6 blocks
Other
Built-in battery required *
1
Inverters of 30 kW or above:
Battery included as standard
*1 For the battery loading procedure, refer to Chapter 8, Section 8.6 "Battery" in the FRENIC-VG User's Manual
(Unit Type / Function Codes Edition).
Figure 5.4.3-2 Traceback Screen
Cursor setting
With two cursors, the size and time can
be measured.