6.6 Flicker
110
6.6.3 IEC Flicker List
Statistics on Pst and Plt are displayed every 10 minutes, along with the
date and time.
• Pst: short interval flicker value
• Plt: long interval flicker value
LIST
FLICKER
• The displayed statistics are for IEC flicker (Pst and Plt), and are displayed
in the list every 10 minutes together with the date and time.
• This is only displayed if Pst, Plt is selected for flicker in [
SYSTEM]-DF2
[MAIN]-[MEASURE].
• EN50160, “Voltage characteristics of electricity supplied by public distri-
bution systems”, specifies a limit of Plt
≤ 1 during 95% of a 1-week
period.