6.6 Flicker
110
6.6.3 IEC Flicker List
Statistics on Pst and Plt are displayed every 10 minutes, along with the
date and time.
Pst: short interval flicker value
Plt: long interval flicker value
LIST
FLICKER
The displayed statistics are for IEC flicker (Pst and Plt), and are displayed
in the list every 10 minutes together with the date and time.
This is only displayed if Pst, Plt is selected for flicker in [
SYSTEM]-DF2
[MAIN]-[MEASURE].
EN50160, “Voltage characteristics of electricity supplied by public distri-
bution systems”, specifies a limit of Plt
1 during 95% of a 1-week
period.