Function Blocks
Function Block Reference Guide 3/99102
2.37 MMA Function Block
Description
The
MMA
label stands for
Min-Max-Average-Sum
. This block is part of the
Calculations
category. It
looks like this graphically on the Control Builder.
Function
Accepts inputs from up to six analog input values (Xl - X6) and calculates these values for output:
MIN - Minimum input value
MAX - Maximum input value
AVG - Average of the 6 input values
SUM - Sum of the 6 input values
DEV - Standard deviation of the 6 input values
ALM - Alarm output for deviations
Turns ON ALM when any input is outside the configured number of standard deviations when the
configuration parameter DEV > 0.
If DEV configured = 0, then:
– no standard deviation is calculated;
– all inputs connected to the block are used to calculate the MIN, MAX, AVG,
AND SUM outputs.
If DEV configured 0, then:
– the standard deviation is calculated for the number of inputs connected to the
block, and
– all inputs connected to the block are used to calculate the MIN, MAX, AVG,
and SUM outputs
.
Continued next page