Function Blocks
Function Block Reference Guide 3/99118
2.45 ON/OFF Function Block
Description
The
ON/OFF
label stands for the
On/Off Control function
.
This block is part of the
Loops
category. It
looks like this graphically on the Control Builder.
Function
Provide ON/OFF control. The output is either ON (100%) or OFF (0%).
Inputs
RSP
= Remote Setpoint (% or EU per SP Units)
TRV
= Track Value Output—1 = ON, 0 = OFF
TRC
= Track Value Command—1 = enable, 0 = disable (Mode = Local Override)
SWI
= Switch Inputs (from LPSW function block)
MDRQI
= External Mode Request (connected to the MDRQO output of a MDSW function block) encoded
as follows:
0.0 = No Change
1.0 = Manual Mode Request
2.0 = Automatic Mode Request
4.0 = Local Setpoint Request
8.0 = Remote Setpoint Request
Continued next page