EasyManuals Logo

Honeywell UMC800 Reference Guide

Honeywell UMC800
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Function Blocks
Function Block Reference Guide 3/9936
2.11 AO Function Block,
continued
Configuration Parameters,
continued
Table 2-8 Analog Output Configuration Parameters
Properties Group Parameter Index# Parameter Description Value or Selection
Block Order
N/A Execution Order for Block
Read Only. See “Configure’
Menu, ”Execution Order” to
change.
Address I/O Module
Address of selected I/O
module (must match model
selection guide)
Enter a value:
from 4 to 10
Channel
Channel on selected I/O
Module
Enter a value:
from 1 to 4
Range Range Hi
1 High Range Value
Engineering Unit - value of
input that corresponds to
100% output value
-99999 to 999999
Default = 100
Range Low
2 Low Range Value
Engineering Unit - value of
input that corresponds to 0%
output value
-99999 to 999999
Default = 0.0
Output mA at range
High
3 Value of mA output that
corresponds to 100% output
signal
(for example: 20mA)
0 to 20
Default = 20
mA at Low
range
4 Value of mA output that
corresponds to 0% output
signal
(for example: 4mA)
0 to 20
Default = 4
Example
Figure 2-10 shows a Function Block Diagram configuration using an AO function block to retransmit an
analog input value. In example A, the output is from a SPP block to an external controller via the AO block.
In example B, the mA output is 4 mA for an analog input of 2000.
NOTE: Reverse scaling is required for duplex control outputs.
Figure 2-10 AO Function Block Example

Table of Contents

Other manuals for Honeywell UMC800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UMC800 and is the answer not in the manual?

Honeywell UMC800 Specifications

General IconGeneral
BrandHoneywell
ModelUMC800
CategoryController
LanguageEnglish

Related product manuals