Function Blocks
3/99 Function Block Reference Guide 61
2.17 DCMP Function Block
Description
The
DCMP
label stands for
Deviation
Compare
. This block is part of the
Calculations
category. It looks
like this graphically on the Control Builder.
Function
Compares up to 6 analog inputs to a + or - user-entered deviation setpoint to a 7
th
input reference value and
sets the output true if any input exceeds the deviation value from the reference value. Output is off if all
inputs are less than the deviation.
Note: When the reference input is the average of the 6 inputs, the block performs deviation from average.
Input
IN1
= Input 1
IN2
= Input 2
IN3
= Input 3
IN4
= Input 4
IN5
= Input 5
IN6
= Input 6
Y
=Reference Input
Note: All inputs should be used or a single value should be connected to multiple inputs. Unused inputs
will default to 0.
Output
OUT = Hi (1) when any input exceeds the specified deviation from the reference value.
Continued next page

Table of Contents

Other manuals for Honeywell UMC800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UMC800 and is the answer not in the manual?

Honeywell UMC800 Specifications

General IconGeneral
BrandHoneywell
ModelUMC800
CategoryController
LanguageEnglish

Related product manuals