Solution 1
Cause
The NVDIMM was previously used in a that did not have a QPI Snoop Configuration of Cluster on Die. The
current has a different QPI Snoop Configuration setting.
Action
Change the QPI Snoop Configuration setting to Cluster on Die.
For more information, see the HPE 8GB NVDIMM User Guide on the Hewlett Packard Enterprise website.
Solution 2
Action
Sanitize all NVDIMMs on Processor X.
For more information, see the HPE 8GB NVDIMM User Guide on the Hewlett Packard Enterprise website.
384-NVDIMM Error – Processor X, DIMM Y
Symptom
NVDIMM Error – Processor X, DIMM Y. NVDIMM set for Channel Interleaving disabled but system configured
for enabled. All NVDIMMs on Processor X are disabled. Action: Sanitize all NVDIMMs on Proc X.
Solution 1
Cause
The NVDIMM was previously installed in a that had Channel Interleaving disabled. The current has Channel
Interleaving enabled.
Action
Enable Channel Interleaving in System Utilities.
For more information, see the HPE 8GB NVDIMM User Guide on the Hewlett Packard Enterprise website.
Solution 2
Action
Sanitize all NVDIMMs on Processor X.
For more information, see the HPE 8GB NVDIMM User Guide on the Hewlett Packard Enterprise website.
385-NVDIMM Error – Processor X, DIMM Y
Symptom
385-NVDIMM Error – Processor X, DIMM Y. NVDIMM set for Channel Interleaving enabled but system
configured for disabled. All NVDIMMs on Processor X are disabled. Action: Sanitize all NVDIMMs on Proc X.
100 384-NVDIMM Error – Processor X, DIMM Y