4.8.6 Installing Cooling Water pipes for the Water Cooling
Module
Prerequisites
Clean the water inlet engineering pipes to avoid impurities entering into the water
cooling module.
Procedure
Step 1 Remove the plugs from the water pipes.
Step 2 Apply thread sealant.
Step 3 Connect water pipes by using a wrench. The connector is G1-1/2 inch with internal
screw threads.
Figure 4-71 Connecting water pipes
----End
4.8.7 (Optional) Connecting the
Humidier Water Inlet Pipe
Context
● A reducing valve must be installed if the inlet water pressure exceeds 0.7 MPa.
● Appliance is intended to be permanently connected to the water mains and
not connected by a hose-set.
Procedure
Step 1 Install the adapter of the
humidier inlet water pipe. Sealing washer is
recommended.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 4 System Installation
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 110