NO TE
You can set LCD password complexity check to Enable or Disable and set the complexity
of the password.
If a password with low complexity is set, the system will display a message indicating that
the password complexity is low and asking you to set a new one. Examples of low
complexity passwords: H#uawei123, Password and openasadminAdmin23@#.
Step 2 Tap Password to access the password change screen and change the password.
----End
12.3.14 How Do I Set Alarm Parameters?
Prerequisites
Before setting the alarm parameters, get familiar with the coupling relationship
among each parameter.
Congurations of temperature and humidity alarms and main board settings for
the air-cooled devices should comply with the following coupling relationships:
Power supply underfrequency alarm threshold < Power supply overfrequency
alarm threshold
Standby power underfrequency alarm threshold < Standby power
overfrequency alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
Context
This section describes how to set an alarm threshold.
All alarm thresholds are congured in the same way. This section describes
how to set the threshold of Return air high temperature alarm for the T/H
sensor.
If you need to change alarm settings, log in as user Admin.
NO TICE
Be careful when conguring alarm parameters. Only professional maintenance
personnel can change alarm settings.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 12 FAQ
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 298