No. Item Note
12 Teamwork control
button
indicates that teamwork control is
disabled.
indicates that teamwork control is
enabled and no teamwork control alarm is
generated.
indicates that teamwork control is
enabled and a teamwork control alarm is
generated.
6.5 Initial Conguration
Log in as the admin user (preset password: 000001) when setting initial
parameters.
6.5.1 Setting T/H Sensor Parameters
Prerequisites
The T/H sensors outside the unit need to be enabled when they are installed;
otherwise, retain the default settings.
This section describes how to enable Cold aisle sensor 1.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
Figure 6-19 T/H Sensor
Step 2 Set Cold aisle sensor 1 to Enable.
Step 3 Set temperature and humidity parameters.
NO TE
You are not advised to modify the parameters that are not listed in the following table.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 6 Power-On Commissioning
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 179