Item NetCol800
0-A045
NetCol800
0-A055/
A060
NetCol80
00-A090
NetCol80
00-A120
Power cable
for the low
temperatur
e
component
(mandatory
when a low
temperatur
e
component
is
congured)
Recommend
ed cable
2 x 1.5
mm
2
2 x 1.5
mm
2
2 x 1.5
mm
2
2 x 1.5
mm
2
NO TE
When the external conditions such as cable layout or ambient temperatures change,
perform verication in accordance with the IEC-60364-5-52 or the local regulations.
The recommended cables are applicable only when the following requirements are met:
The cables are routed over a ladder or bracket in a single layer (E or F in IEC
60364-5-523). The distance between cables is greater than twice the cable diameter.
The AC voltage loss is less than 3%.
Single- or multi-core 90°C-resistant copper exible cables are used.
Table 4-4 Power cable terminal requirements
Item
NetCol8000-A045/A055/A060/A090/A120
Terminal L1/L2/L3/N PE
Connection mode Cord end terminal OT terminal
Torque 2.0 N·m 4.5 N·m
4.3 Unpacking and Checking
Prerequisites
Move the smart cooling product to a place closest to the installation position and
then unpack it to facilitate cabinet movement and avoid cabinet damage.
Procedure
Step 1 Verify that the cabinet package is intact. If any damage is found, notify the carrier
immediately.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 4 System Installation