Figure 4-72 Connecting a water inlet pipe
NO TICE
When plastic materials such as PA66 are used, the recommended torque is 5
N·m.
When metal materials are used, the recommended torque is 10 N·m. A sealing
washer must be used when a union is used.
Step 2 Install the humidier inlet water pipe to the adapter.
Step 3 Bind the
humidier inlet water pipe to the sheet metal of the water inlet pipe
using cable ties.
Step 4 Clean the engineering pipes before connecting the water inlet pipe to the engineer
pipe to avoid impurities entering into the
humidier.
Step 5 Connect the water inlet pipe to the engineer pipe and wrap the pipe with thermal
insulation foam.
----End
4.8.8 Connecting the Drainpipe
Context
The following uses hose bottom routing as an example to describe how to connect
drainpipes.
Bottom Pipe Routing
Step 1 Install the water pipe conversion adapter and seal it with sealant.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 4 System Installation
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 111