Item NetCol8000-
A060D
NetCol8000-
A060U
NetCol8000-
A120D
Maximum
operating current
(A) - dual power
supplies
● With heating
and
humidication
– Active route:
45
– Standby
route: 41
● Without
heating and
humidication
– Active route:
41
– Standby
route: 41
● With heating
and
humidication
– Active
route: 45
– Standby
route: 41
● Without
heating and
humidication
– Active
route: 41
– Standby
route: 41
● With heating
and
humidication
– Active route:
90
– Standby
route: 82
● Without
heating and
humidication
– Active route:
82
– Standby
route: 82
Dimensions (H x
W x D) (mm)
2000 x 1100 x
1000
2000 x 1100 x
1000
2000 x 2200 x
1000
Air lter level G4 G4 G4
Net weight (kg) 400 416 764
a: Tested under rated working conditions (indoor dry-bulb temperature: 35°C,
relative humidity: 26%; outdoor temperature: 35°C).
3.2 Outdoor Unit
Figure 3-1 NetCol500-A dimensions
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 3 Technical Specications
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 40