Item NetCol8000-A055D
Maximum operating current (A) - dual
power supplies
● With heating and humidication
– Active route: 45
– Standby route: 41
● Without heating and humidication
– Active route: 41
– Standby route: 41
Dimensions (H x W x D) (mm) 2000 x 900 x 1000
Air lter level G4
Net weight (kg) 354
a: Tested under rated working conditions (indoor dry-bulb temperature: 35°C,
relative humidity: 26%; outdoor temperature: 35°C).
Table 3-3 Technical specications of NetCol8000-A060/NetCol8000-A120
Item
NetCol8000-
A060D
NetCol8000-
A060U
NetCol8000-
A120D
Power supply 380–415 V AC, 3-phase, 50 Hz/60 Hz
Number of fans 1 1 2
Total cooling
capacity (kW)
a
60 60 120
Sensible cooling
capacity (kW)
a
60 60 120
Air volume (m
3
/h)
15000 14500 30000
(Optional)
Reheating
capacity (kW)
a
6 6 12
(Optional)
Humidication
capacity (kg/h)
a
6 6 10
Maximum
operating current
(A) - single power
supply
● With heating
and
humidication:
45
● Without
heating and
humidication:
41
● With heating
and
humidication:
45
● Without
heating and
humidication:
41
● With heating
and
humidication:
90
● Without
heating and
humidication:
82
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 3 Technical Specications
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 39