Item NetCol8000-
A045D
NetCol8000-
A045U
NetCol8000-
A090D
Maximum
operating current
(A) - dual power
supplies
● With heating
and
humidication
– Active route:
40
– Standby
route: 36
● Without
heating and
humidication
– Active route:
36
– Standby
route: 36
● With heating
and
humidication
– Active route:
40
– Standby
route: 36
● Without
heating and
humidication
– Active route:
36
– Standby
route: 36
● With heating
and
humidication
– Active route:
80
– Standby
route: 72
● Without
heating and
humidication
– Active route:
72
– Standby
route: 72
Dimensions (H x
W x D) (mm)
2000 x 900 x 900 2000 x 900 x 900 2000 x 1800 x
1000
Air lter level G4 G4 G4
Net weight (kg) 337 334.5 643
a: Tested under rated working conditions (indoor dry-bulb temperature: 35°C,
relative humidity: 26%; outdoor temperature: 35°C).
Table 3-2 Technical specications of NetCol8000-A055
Item
NetCol8000-A055D
Power supply 380–415 V AC, 3-phase, 50 Hz/60 Hz
Number of fans 1
Total cooling capacity (kW)
a
55
Sensible cooling capacity (kW)
a
55
Air volume (m
3
/h)
13000
(Optional) Reheating capacity (kW)
a
6
(Optional) Humidication capacity
(kg/h)
a
6
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 3 Technical Specications
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 38