Temperature Setpoint
(°C)
Lower Limit of
Humidity Setpoint (%
RH)
Upper Limit of
Humidity Setpoint (%
RH)
19 19.2 80
20 18.1 80
21 17 80
22 16 80
23 15 80
24 15 75.3
25 15 70.9
26 15 66.8
27 15 63
28 15 59.4
29 15 56.1
30 15 52.9
31 15 50
32 15 47.2
33 15 44.6
34 15 42.2
35 15 39.9
36 15 37.8
37 15 35.8
38 15 33.9
39 15 32.1
40 15 30.4
41 15 28.9
42 15 27.4
43 15 26
44 15 24.7
45 15 23.4
----End