Alarm ID Alarm Name Alarm
Severity
Possible Cause Solution
A180-01 Humidier exceed
runtime alarm
Warning The accumulated
runtime of the wet
lm of the humidier
exceeds the alarm
threshold.
Maintain or replace
the wet lm of the
humidier and clear
the accumulated
runtime.
A183-01 Outdoor fan 1 outdoor
temperature sensor
fault
Outdoor fan 2 outdoor
temperature sensor
fault
Major ● The cables to the
temperature sensor
are loose or
damaged.
● The temperature
sensor is faulty.
1. Check the cables to
the temperature
sensor.
2. Maintain or replace
the temperature
sensor.
A184-01 Compressor 1
preheating alarm
Compressor 2
preheating alarm
Warning ● The compressor is
preheated before
startup.
● The compressor is
preheated after a
power failure.
1. Start the
equipment after
preheating is
complete, or set
the Compressor
preheating
parameter to
O
to stop preheating.
2. Wait until
compressor
preheating is
complete, or set
the Compressor
preheating
parameter to
O
to stop preheating.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 10 Alarm Reference
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 237