Alarm ID Alarm Name Alarm
Severity
Possible Cause Solution
A28D-01 Compressor 1 low
suction pressure alarm
Compressor 2 low
suction pressure alarm
Major ● The refrigerant
leaks.
● The solenoid valve
is faulty.
● The pressure
displayed is
dierent from the
actual pressure.
● The
lter dryer is
blocked.
● The expansion
valve is blocked or
stuck, or the
expansion valve coil
and cable
connections are
faulty.
● The indoor fan is
faulty.
● The ambient
temperature is
below the lower
threshold.
1. Identify and repair
the leaking point,
and rell
refrigerant after
maintenance.
2. Maintain or replace
the solenoid valve
coil or the solenoid
valve.
3. Calibrate or replace
the pressure sensor.
4. Maintain or replace
the
lter dryer.
5. Maintain or replace
the expansion valve
or the coil, and
reconnect cables.
6. Maintain or replace
the indoor fan.
7. Measure the
ambient
temperature.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 10 Alarm Reference