The smart cooling products should be placed as far away from oces as
possible, and noise control measures should be taken.
If the cap is congured, reserve space on the top of the indoor unit. The
height of the reserved space must be greater than that of the cap. For details,
see 4.11.5 (Optional) Installing a Cap (Applicable to Upow Units).
Figure 4-3 Layout of bottom pipe routing (1)
(1) NetCol8000-A
NO TE
The height of the raised oor for downow units must be greater than 550 mm. (The
550 mm space under the oor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.) Properly determine the positions for routing
pipes and cables to avoid interference.
The height of raised
oors is greater than 300 mm for upow units.
W indicates the distance between smart cooling products. The minimum distance is 300
mm for upow units or 500 mm for downow units.
L indicates the front maintenance distance for the device. The minimum distance is 900
mm for the NetCol8000-A045, NetCol8000-A055, and NetCol8000-A090, or 1100 mm
for the NetCol8000-A060 and NetCol8000-A120. If the front distance cannot meet the
requirements, remove the front door for maintenance. The minimum distance is 800
mm.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 4 System Installation
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 54