● The smart cooling products should be placed as far away from oces as
possible, and noise control measures should be taken.
● If the cap is congured, reserve space on the top of the indoor unit. The
height of the reserved space must be greater than that of the cap. For details,
see 4.11.5 (Optional) Installing a Cap (Applicable to Upow Units).
Figure 4-3 Layout of bottom pipe routing (1)
(1) NetCol8000-A
NO TE
● The height of the raised oor for downow units must be greater than 550 mm. (The
550 mm space under the oor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.) Properly determine the positions for routing
pipes and cables to avoid interference.
● The height of raised
oors is greater than 300 mm for upow units.
● W indicates the distance between smart cooling products. The minimum distance is 300
mm for upow units or 500 mm for downow units.
● L indicates the front maintenance distance for the device. The minimum distance is 900
mm for the NetCol8000-A045, NetCol8000-A055, and NetCol8000-A090, or 1100 mm
for the NetCol8000-A060 and NetCol8000-A120. If the front distance cannot meet the
requirements, remove the front door for maintenance. The minimum distance is 800
mm.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 4 System Installation
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 54