7: BASIC INSTRUCTIONS
OPENNET CONTROLLER USERS MANUAL 7-19
Examples: DC= and DC (Data Register Comparison)
Ladder Diagram 1
Timing Chart
DC=
5
D2
DC>=
3
D2
Input I1
ON
OFF
D10 Value
Output Q0
ON
OFF
Output Q1
ON
OFF
Prgm Adrs Instruction Data
0
1
2
3
4
5
6
7
8
9
LOD
MOV(W)
DC=
OUT
DC
OUT
I1
D10
D2
D2
5
Q0
D2
3
Q1
Program List
44 553 35210
I1
REPS1
D10
D1
D2
MOV(W)
10 37 22
D2 Value
04 553 35210 10 33 22
Output Q0 is on when data register D2
value is 5.
Output Q1 is turned on when data register
D2 value is 3 or more.
Q0
Q1
Ladder Diagram 2
Output Q0 is on when data register D30 value is 500.
DC=
500
D30
Timing Chart
Output Q0
ON
OFF
400 210 210 0 500
D30 Value
I1
REPS1
D50
D1
D30
MOV(W)
500 500 700
Q0
Ladder Diagram 3
DC>=
350
D15
I1
REPS1
D0
D1
D15
MOV(W)
Output Q1 is on when data register D15 value is 350 or more.
Timing Chart
Output Q1
ON
OFF
200 249 200 350 390
D15 Value
355 521 600
Q1
Ladder Diagram 4
DC>=
150
D20
DC>=
100
D20
Q0
I1
REPS1
D100
D1
D20
MOV(W)
Output Q2 is on while data register D20 value is between
149 and 100.
Timing Chart
Output Q0
ON
OFF
90 150 80 160 110
D20 Value
120 180 95
Output Q2
ON
OFF
Q2
Q0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC OpenNet series and is the answer not in the manual?

IDEC OpenNet series Specifications

General IconGeneral
BrandIDEC
ModelOpenNet series
CategoryController
LanguageEnglish

Related product manuals