15: WEEK PROGRAMMER INSTRUCTIONS
15-6 OPENNET CONTROLLER USERS MANUAL
Example: Interval comparison with ON/OFF times on different days — 3
The output is turned on at 11:00 a.m. on Friday through Sunday, and is turned off at 2:00 a.m. on the following day.
Example: Interval comparison with ON/OFF times extending over three days
To keep the output on for more than two days, use the ICMP (interval compare greater than or equal to) instruction in
combination with the WKCMP ON/OFF instructions. This example turns on the output at 8:00 a.m. on Monday and turn it
off at 7:00 p.m. on Friday.
D1
Q0
S1
99
M8125
WKCMP
ON
S2
1100
S3
0
D1
Q0
S1
99
WKCMP
OFF
S2
200
S3
0
M8125 is the in-operation output special internal relay.
S1 (99) specifies Friday through Monday.
WKCMP ON turns on output Q0 at 11:00 a.m. on Friday
through Sunday.
WKCMP OFF turns off output Q0 at 2:00 a.m. on the next day.
Sun
Mon Tue Wed Thu Fri Sat
Output Q0
S1: Same constant value to designate consecutive days
S2: Constant values; ON time > OFF time
S3: Same constant value 0
D1: Same operand
11:00 2:00
ON
11:00 2:00
ON
11:002:00
ON
D1
M0
S1
6
M8125
WKCMP
ON
S2
800
S3
0
D1
M0
S1
6
WKCMP
OFF
S2
0
S3
0
M8125 is the in-operation output special internal relay.
S1 (6) specifies Monday and Tuesday.
WKCMP ON turns on M0 at 8:00 a.m. on Monday.
WKCMP OFF turns off M0 at 0:00 a.m. on Tuesday.
D8011 contains the current day of week data. S1 (4) specifies
Thursday. S3 (2) specifies Tuesday. See page 15-7. M1 remains
on from Tuesday through Thursday.
S1 (32) specifies Friday.
WKCMP ON turns on M2 at 0:00 a.m. on Friday.
WKCMP OFF turns off M2 at 19:00 on Friday.
While M0, M1, or M2 is on, output Q0 is turned on.
Sun
Mon Tue Wed Thu Fri Sat
Output Q0
8:00
ON
19:00
M0 M1 M2
D1
M1
S1
4
ICMP>=(W) S2
D8011
S3
2
D1
M2
S1
32
WKCMP
ON
S2
0
S3
0
D1
M2
S1
32
WKCMP
OFF
S2
1900
S3
0
M0
M1
M2
Q0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC OpenNet series and is the answer not in the manual?

IDEC OpenNet series Specifications

General IconGeneral
BrandIDEC
ModelOpenNet series
CategoryController
LanguageEnglish

Related product manuals