37
6 Electrical connection
Use shrink tubing to insulate the shield and Shield-Kon® connector
1
6.2.2 Conductor cross-sections for base unit and power supply unit
The terminals on the base unit and power supply unit are plug-in screw termi-
nals.
^
1.Shield-Kon is a registered trademark of THOMAS & BETTS INTERNATIONAL, Inc.,
Wilmington Del., US.
60 mm
Shield-Kon® connector
Ferrule Conductor cross sec-
tion
Length to
strip
minima l Maximum
without ferrule
Power supply unit voltage supply 0.2 mm
²
2.5 mm
²
7mm
Power supply unit relay switching
outputs
0.2 mm
²
2.5 mm
²
7mm
Base unit 0.14 mm
2
1.5 mm
2
7mm
Ferrule without lip
Power supply unit voltage supply 0.25 mm
2
2.5 mm
²
7mm
Power supply unit relay switching
outputs
0.25 mm
2
2.5 mm
²
7mm
Base unit 0.25 mm
2
1.5 mm
2
7mm
with ferrule with lip
Power supply unit voltage supply 0.25 mm
2
2.5 mm
²
7mm
Power supply unit relay switching
outputs
0.25 mm
2
2.5 mm
²
7mm
Base unit 0.25 mm
2
0.5 mm
2
7mm
Rigid
Power supply unit voltage supply 0.2 mm
²
2.5 mm
²
7mm
Power supply unit relay switching
outputs
0.2 mm
²
2.5 mm
²
7mm
Base unit 0.14 mm
2
1.5 mm
2
7mm