MULTICAL®603
KamstrupA/S∙Technicaldescription∙5512‐2029_A1_GB_06.2017
33
Thebelow‐mentionedtableliststhetarifftypes,forwhichMULTICAL
603canbeconfiguredandshowsthetariff
typesavailableforeachmetertype.
EE=00Noactivetariff
Ifnotarifffunctionisrequired,youselecttheset‐upEE=00.
Thetarifffunctioncan,however,atalaterstagebeactivatedthroughr econfigurationvia METERTOOLHCW(se e
Technicaldescription5512
‐2096).
EE=11Power‐controlledtariff
Ifthecurrentpower(P)exceedsTL2butislowerthanorequaltoTL3,energyiscountedinTA2paralleltothemain
register.IfthecurrentpowerexceedsTL3butislowerthanorequaltoTL4,energyiscountedinTA3parallel
tothe
mainregister.IfthecurrentpowerexceedsTL4,energyiscountedinTA4paralleltothemainregister.
PTL2
Accumulationinmainregisteronly
TL4TL3TL2
TL3PTL2
AccumulationinTA2andmainregister
TL4PTL3
AccumulationinTA3andmainregister
PTL4
AccumulationinTA4andmainregister
Settingupdata,TL3mustbehigherthanTL2andTL4mustbehigherthanTL3.
Thepowercontrolledtariffise.g.usedasabasisfortheindividualheatconsumer’sconnectionfee.Furthermore,this
tarifftypecanprovidevaluablestatisticaldataiftheheatingstationconsidersnewconstructionactivities.
EE= Tarifftype Function
Heatmeter
Metertype2
Heat/coolingmeter
Metertype3
Heatmeter
Metertype4
Coolingmeter
Metertype5
Heat/coolingmeter
Metertype6
Volumemeter
Metertype7
00 Noactivetariff Nofunction
11 Powertariff
EnergyisaccumulatedinTA2,TA3andTA4onthebasisofthepower
limitsenteredinTL2,TL3andTL4
12 Flowtariff
EnergyisaccumulatedinTA2,TA3andTA4onthebasisofthe flow
limitsenteredinTL2,TL3andTL4
13 t1‐t2tariff
EnergyisaccumulatedinTA2,TA3andTA4onthebasisofthet‐
limitsenteredinTL2,TL3andTL4
14 Inlettemperaturetariff
EnergyisaccumulatedinTA2,TA3andTA4onthebasisofthet1‐
limitsenteredinTL2,TL3andTL4.
15 Outlettemperaturetariff
EnergyisaccumulatedinTA2,TA3andTA4onthebasisofthet2‐
limitsenteredinTL2,TL3andTL4.
19 Timec ontrolledtariff
TL2=StarttimeofTA2
TL3=StarttimeofTA3
TL4=StarttimeofTA4
20
Heat/coolingvolumetariff
(TL2,TL3andTL4arenotused)
Volume(V1)isdividedintoTA2forheat(t1t2)andTA3forcooling
(t1t2).Forheat/coolingmeters,metertypes3and6,theenergy
accumulation also depends onΘ
HC
(TA4 is not used in this tariff
type).
21 PQ‐tariff
EnergyatPTL2issavedinTA2,andenergyatQTL3issavedinTA3