EE=12Flowcontrolled tariff
Ifthecurrentwaterflow(Q)exceedsTL2butislowerthanorequaltoTL3,energyiscountedinTA2paralleltothe
mainregister.IfthecurrentwaterflowexceedsTL3butislowerthanorequaltoTL4,energyiscountedinTA3 parallel
tothemainregister.IfthecurrentwaterflowexceedsTL4,energyiscountedinTA4paralleltothemainregister.
QTL2
Accumulationinmainregisteronly
TL4TL3TL2
TL3QTL2
AccumulationinTA2andmainregister
TL4QTL3
AccumulationinTA3andmainregister
QTL4
AccumulationinTA4andmainregister
Settingupdata,TL3mustbehigherthanTL2andTL4mustbehigherthanTL3.
Theflowcontrolledtar iffise.g.usedasabasisfortheindividualheatconsum er’sconnectionfee.Furthermore,this
tarifftypecanprovidevaluablestatisticaldataiftheheatingstationconsidersnewconstructionactivities.
Wheneitherpowerorflowtariffisusedyouobtainanoverviewofthetotalconsumptioncomparedtothepartofthe
consumptionusedabovetarifflimits.
EE=13t1‐t2tariff(Θ)
Ifthecurrentt1‐t2(Θ)islowerthanTL2butexceedsorisequal
toTL3,heatenergyiscountedinTA2paralleltothe
mainregister.IfthecurrentcoolingbecomeslowerthanTL3butishigherthanorequaltoTL4,energyiscountedin
TA3paralleltothemainregister.Ifthecurrentt1‐t2(Θ)islowerthanTL4,
energyiscountedinTA4paralleltothe
mainregister.
ΘTL2
Accumulationinmainregisteronly
TL4TL3TL2
TL3ΘTL2
AccumulationinTA2andmainregister
TL4ΘTL3
AccumulationinTA3andmainregister
ΘTL4
AccumulationinTA4andmainregister
Settinguptarifflimits,TL3mustbelowerthanTL2andTL4mustbelowerthanTL3.
Thet1‐t2tariffcanbeusedasabasisofweightedusercharge.LowΘ(smalldifferencebetweeninletandoutlet
temperatures)isuneconomicalfortheheatsupplier.