Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 101
33.110 Motor voltage Unit: V
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 1500
def.: 0
Only for asynchronous motors.
This is used to set the nominal motor voltage U
M,N
for either the star or triangle
connection.
33.111 Motor cos phi Unit: 1
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0.5 Own value
(to be entered!)
max.: 1
def.: 0
Only for asynchronous motors.
The value from the motor's type plate data has to be entered here for the
power factor cos phi.
33.200 Stator inductance Unit: H
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 1
def.: 0
For synchronous motors only.
The stator inductance can be optimised here if the automatically determined
value (motor identification) is insufficient.
33.201 Nominal flux Unit: mVs
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 10000
def.: 0
For synchronous motors only.
The nominal flux can be optimised here if the automatically determined value
(motor identification) is insufficient.