Parameters
100 Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN
33.034 Motor speed Unit: rpm
Relationship
to parameter:
34.120
5.075
Parameter
manual:
P. xy
Transfer status:
1
min:
0 Own value
(to be entered!)
max: 10000
def.: 0
The value from the motor's type plate data has to be entered here for the
nominal motor rotation speed n
M,N
.
33.035 Motor frequency Unit: Hz
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 10 Own value
(to be entered!)
max.: 400
def.: 0
This is where the nominal motor frequency f
M,N
is set.
33.050 Stator resistance
Unit: Ohm
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 100
def.: 0.001
The stator resistance can be optimised here, if the automatically determined
value (motor identification) is insufficient.
33.105 Leakage inductance Unit: H
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 1
def.: 0
Only for asynchronous motors.
Here the leakage inductance can be optimised if the automatically calculated
value (of motor identification) isn't sufficient.