Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 99
33.015 R optimisation Unit: %
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 200
def.: 100
If necessary, this parameter can be used to optimise the start-up behaviour.
33.016 Motor phases monitoring Unit: integer
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 1
def.: 1
(V 03.72 and higher)
The "Motor connection interrupted" error monitoring (error -45) can be
disabled with this parameter.
0 = Monitoring disabled
1 = Monitoring enabled
33.031 Motor current Unit: A
Relationship
to parameter:
5.070
Parameter
manual:
P. xy
Transfer status:
1
min.:
0 Own value
(to be entered!)
max.: 150
def.: 0
This is used to set the nominal motor current I
M,N
for either the star or triangle
connection.
33.032 Motor rating Unit: W
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
1
min.: 0 Own value
(to be entered!)
max.: 55000
def.: 0
A performance value [W] P
M,N
has to be set here that corresponds to the
nominal motor rating.