Parameter Name / value range / [default seng] Info
0x282B:002
(P125.02)
Inverter diagnoscs: Acve setpoint source
(Inverter diag.: Acve setpoint)
•
Read only
Display of the setpoint source that is currently acve.
0 Not selected
1 Analog input 1
2 Analog input 2
3 Keypad Setpoint
4 HTL input
5 Network Setpoint
11 Setpoint preset 1
12 Setpoint preset 2
13 Setpoint preset 3
14 Setpoint preset 4
15 Setpoint preset 5
16 Setpoint preset 6
17 Setpoint preset 7
18 Setpoint preset 8
19 Setpoint preset 9
20 Setpoint preset 10
21 Setpoint preset 11
22 Setpoint preset 12
23 Setpoint preset 13
24 Setpoint preset 14
25 Setpoint preset 15
31 Segment preset 1
32 Segment preset 2
33 Segment preset 3
34 Segment preset 4
35 Segment preset 5
36 Segment preset 6
37 Segment preset 7
38 Segment preset 8
39 Last segment
50 Motor potenometer
51 PID setpoint (from version 04.00)
201 Internal value (from version 05.00)
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
0x282B:003
(P125.03)
Inverter diagnoscs: Keypad LCD status
(Inverter diag.: Keypad LCD stat.)
•
Read only
Bit-coded state of the keypad status displays.
Bit 0 LOC 1 ≡ local keypad control acve.
Bit 1 REM 1 ≡ remote control via terminals, network, etc. acve.
Bit 2 MAN 1 ≡ manual setpoint selecon via keypad acve.
Bit 3 Auto 1 ≡ automac setpoint selecon via terminals, network, etc. acve.
Bit 4 Set 1 ≡ a parameter seng has been changed but not been saved yet in the
memory module with mains failure protecon.
Diagnoscs and fault eliminaon
Diagnoscs parameter
Inverter diagnoscs
116