6. Set the RPI rate.
The example shows the default seng of the RPI rate with "10.0" ms. This means that
the inverter is queried every 10 milliseconds by the scanner. For the most inverter appli-
caons, it is not required to query the inverter more frequently.
The minimum value for inverters of the i series is 4.0 ms.
7. Acvate/deacvate "Use Unicast Connecon over EtherNet/IP".
The inverter supports "Unicast Connecon over EtherNet/IP". The acvaon of this
funcon causes a faster overall network power. The use of this funcon, however, can
make the error correcon for managed switches more complicated.
8. Make oponal sengs.
a) Acvang "Inhibit Module" inhibits the inverter.
b) Acvang "Major Fault On Controller If Connecon Fails While in Run Mode"
switches the inverter to "error" if the EtherNet/IP connecon to the inverter gets lost
during operaon.
9. Click "OK".
The network conguraon of the inverter is now completed.
In the
navigaon tree ("Controller Organizer") under "Controller à Controller Tags",
assembly tags are generated.
In the sample conguraon with the "My_EIP_i550" inverter, these three assembly tags
are generated:
"My_EIP_i550:C" for the conguraon assembly
"My_EIP_i550:I" for the input assembly
"My_EIP_i550:O" for the output assembly
By clicking [+] in front of the assembly names, the display of the assemblies is extended.
Conguring the network
EtherNet/IP
Process data transfer
334