EasyManua.ls Logo

Lenze i55AE155F

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fuse data
Inverter I55AE315F
I55AE318F
I55AE322F I55AE330F I55AE337F
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class
J, T, R
-
Max. rated current A 70 - - -
Circuit breaker
Characteriscs - - - -
Max. rated current A - - - -
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class J, T, R
Max. rated current A 70 70 80 100
Circuit breaker
Characteriscs - - - -
Max. rated current A - - - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Fuse data
Inverter
I55AE345F
I55AE355F
I55AE375F
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon
Fuse
Characteriscs -
Max. rated current A - -
Circuit breaker
Characteriscs - -
Max. rated current A - -
operaon with mains choke
Fuse
Characteriscs
all acc. to UL 248 / Class J, T, R
acc. to UL 248 / Class J (recommended: HSJ by
Mersen)
Max. rated current A 125 200
Circuit breaker
Characteriscs - -
Max. rated current A - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 400 V
44

Table of Contents

Related product manuals