EasyManua.ls Logo

Lenze i55AE155F

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fuse data
Inverter I55AE355F
I55AE375F
Cable installaon in compliance with EN 60204-1
Installaon method F
operaon
Fuse
Characteriscs -
Max. rated current A -
Circuit breaker
Characteriscs -
Max. rated current A -
operaon with mains choke
Fuse
Characteriscs gR
Max. rated current A 160
Circuit breaker
Characteriscs -
Max. rated current A -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Fuse data
Inverter I55AE137F
I55AE155F
I55AE175F
I55AE211F
I55AE215F
I55AE222F
I55AE230F
I55AE240F
I55AE255F
I55AE275F I55AE311F
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC all acc. to UL 248 / Class J, T, R
Max. rated current A 15 25 40 40
Circuit breaker
Characteriscs -
Max. rated current A - 25 35 -
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC all acc. to UL 248 / Class J, T, R
Max. rated current A 15 25 40 40
Circuit breaker
Characteriscs -
Max. rated current A - 25 35 -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 480 V
54