Example for operang mode
•
The keypad is set as standard setpoint source.
•
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
•
The switches S2 ... S4 serve to switch over to the presets 1 ... 7 (see the following table).
Connecon plan funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3 S4
Switch S1 Run
Switches S2 ... S4 Preset selecon:
S2 S3 S4
O O O Keypad setpoint
On O O Preset value 1
O On O Preset value 2
On On O Preset value 3
O O On Preset value 4
On O On Preset 5
O On On Preset 6
On On On Preset value 7
Parameter Name Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2631:018 (P400.18) Acvate preset (bit 0) Digital input 2 [12]
0x2631:019 (P400.19) Acvate preset (bit 1) Digital input 3 [13]
0x2631:020 (P400.20) Acvate preset (bit 2) Digital input 4 [14]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Keypad [1]
0x2911:001 (P450.01) Frequency setpoint presets: Preset 1 10 Hz
0x2911:002 (P450.02) Frequency setpoint presets: Preset 2 15 Hz
0x2911:003 (P450.03) Frequency setpoint presets: Preset 3 20 Hz
0x2911:004 (P450.04) Frequency setpoint presets: Preset 4 25 Hz
0x2911:005 (P450.05) Frequency setpoint presets: Preset 5 30 Hz
0x2911:006 (P450.06) Frequency setpoint presets: Preset 6 35 Hz
0x2911:007 (P450.07) Frequency setpoint presets: Preset 7 40 Hz
If the frequency presets 8 ... 15 are required as well, the digital input 5 must be
addionally assigned to the "Acvate preset (bit 3)" funcon and the terminal
DI5 must be interconnected accordingly.
Flexible I/O conguraon
Setpoint change-over
Setpoint source of preset setpoints