Parameter Name / value range / [default seng] Info
0x2631:051
(P400.51)
Funcon list: Select sequence (bit 1)
(Funcon list: Seq: Select. b1)
Seng can only be changed if the inverter is inhibi-
ted.
From version 03.00
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Select sequence (bit 1)" funcon.
Selecon bit with the valency 2
1
for the bit-coded selecon of a
sequence.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
Notes:
The selected sequence is not started automacally.
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is available.
For an edge-controlled start, the funcon "Start sequence"
0x2631:031 (P400.31) is available.
0 Not connected
0x2631:052
(P400.52)
Funcon list: Select sequence (bit 2)
(Funcon list: Seq: Select. b2)
Seng can only be changed if the inverter is inhibi-
ted.
From version 03.00
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Select sequence (bit 2)" funcon.
Selecon bit with the valency 2
2
for the bit-coded selecon of a
sequence.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
Notes:
The selected sequence is not started automacally.
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is available.
For an edge-controlled start, the funcon "Start sequence"
0x2631:031 (P400.31) is available.
0 Not connected
0x2631:053
(P400.53)
Funcon list: Select sequence (bit 3)
(Funcon list: Seq: Select. b3)
Seng can only be changed if the inverter is inhibi-
ted.
From version 03.00
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Select sequence (bit 3)" funcon.
Selecon bit with the valency 2
3
for the bit-coded selecon of a
sequence.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
Notes:
The selected sequence is not started automacally.
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is available.
For an edge-controlled start, the funcon "Start sequence"
0x2631:031 (P400.31) is available.
0 Not connected
Flexible I/O conguraon
Sequencer control funcons
590