16.1.5.5 Reset fault
This command resets a pending fault if the cause of the fault has been eliminated.
The pulse inhibit r
emains acve (pulses of the inverter are inhibited).
A chang
eover to the "Switch-on inhibited" device status takes place (switch-on inhibit
remains acve).
A From all states
B Power secon inhibited (pulse inhibit)
C Power secon enabled
Bit paern in the CiA 402 control word (0x6040)
Bit 15 ... 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved
(specic)
Reset fault Operang mode dependent Operaon
enabled
Acvang
quick stop
Establish read-
iness f
or oper-
aon
Switch-on
X 0↗1 X X X X X X X
X = state is not relevant