7.15 Monitoring
Overview of necessary parameterisaon for
cross-funconal monitoring.
The associated dialogue contains:
•
The seng parameters
•
The status
•
The acvaon opon
7.15.1 Web break monitoring
Only acvate web break monitoring when the calculated diameter corresponds
t
o the real diameter!
In the event of a web break:
•
The c
alculated diameter changes in the opposite direcon to that of the winding direcon.
•
The circumferenal speed no longer corresponds to the line speed signal.
When the parameter Web break detecon window size = 0 or = 2, a diameter change in the
opposite direcon to that of the winding direcon is only sll permissible within the window
congured in the parameter W
eb break detecon window size. 40x5051:072
How to acvate web break monitoring:
1.Set bit 24 of parameter Control words = TRUE. 0x5050:010
The last valid diameter value is maintained as soon as a web break is idened.
Funcon Parameter index Bit Bit status
Web break monitoring detected 0x5050:110 24 TRUE
Diagnose winding direcon 0x5050:110 17 TRUE
Loading a start diameter that signicantly deviates from the real diameter in the direcon
opposite the winding direcon can unintenonally trigger the monitoring funcon. This can
happen, for example, when a standard diameter of 50 [%] is loaded at the rewinder and the
real diameter is only 45 [%]. In such a case, the acvated web break monitoring funcon will
prevent the diameter value from changing to the real 45 [%].
Parameter
Address Name / seng range / [default seng] Info
0x5051:073 Web break monitoring mode
0 Unexpected diameter change+dancer in limit
posion
1 Dancer in limit posion
2 Unexpected diameter change
7.15.1.1 Monitoring based on the change in diameter
Parameter
Address Name / seng range / [default seng] Info
0x5051:011 Winding direcon with line velocity > 0
false Rewinder Rewind acve
true Unwinder Unwind acve
Conguring the "Winder Dancer" TA
Monit
oring
Web break monitoring