17.15 Heatsink temperature monitoring
In order to avoid an impermissible heang of the servo inverter, the temperature of the heat-
sink is de
tected and monitored.
The temperature of the heatsink is measured in the temperature range of 0 ...
80 °C with a t
olerance of -2 ... +4 °C. Beyond this temperature range, the meas-
uring accuracy decreases faster.
Parameter
Address Name / seng range / [default seng] Info
0x2D84:001,
004, 006
Heatsink temperature: Heatsink temperature
R
ead only: x.x °C
Display of the current heatsink temperature.
0x2D84:002 Heatsink temperature: Heatsink temperature: Warn-
ing thr
eshold
50.0 ... [90.0] ... 100.0 °C
Warning threshold for temperature monitoring.
If the heatsink temperature exceeds the threshold set here, the inver-
ter outputs a warning.
The warning is reset with a hysteresis of approx. 5 °C.
If the heatsink temperature increases further and exceeds the non-
adjustable error threshold (100 °C), the inverter changes to the " Fault
" device status. The inverter is disabled and thus any further opera-
on is stopped.
17.16 Update device rmware
17.16.1 Manual rmware download with »EASY Starter (rmware loader)«
17.16.1.1
Download via Ethernet connecon
Parameter
Address Name / seng range / [default seng] Info
0x243C:001 Device: Ethernet commands: Device: Start rmware
update
Seng can only be changed if the inverter is inhibi-
t
ed.
0 O/Ready
1 On/Start
4 Acon cancelled
20 20%
40 40%
60 60%
80 80%
Device
funcons
Update device rmware
Manual rmware download with »EASY Starter (rmware loader)«