18.3 Mains failure control
P
arameter
Address Name / seng range / [default seng] Info
0x2D66:001 Mains failure control: Enable funcon 1 = enable mains failure control.
0 Disabled
2 Enabled
0x2D66:002 Mains failure control: DC-bus acvaon level
60 ... [75] ... 90
%
Threshold below which the mains failure control is acvated if it is ena-
bled (0x2D66:001 = 1).
100 % ≡ nominal DC-bus voltage
Recommended seng:
In g
eneral: 5 ... 10 % above the error threshold for undervoltage (dis-
play in 0x2540:003).
230-V devices: 72 %
400/480-V devices: 82 %
0x2D66:011 Mains failure control: Filter me
0.00 ... [0.00] ... 60.00
s
0x2D66:012 Mains failure control: Ramp max. torque
0.0 ... [30.0] ... 3276.7 %
0x2D66:013 Mains failure control: Ramp me
0.10 ... [1.00] ... 5.00 s
0x2D66:014 Mains failure control: Actual DC-bus voltage
Read only: x.xxx V
Addional
funcons
Mains failure control
385