EasyManua.ls Logo

Lenze i950

Lenze i950
496 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13.4 V/f
characterisc control for asynchronous motor (VFC open loop)
The V/f characterisc control is a motor control for convenonal frequency inverter applica-
ons. It is based on a simple and robust control mode for the operaon of asynchronous
motors with a linear or square-law load torque characterisc (e.g. fan). Because of the mini-
mal parameterisaon eort, such applicaons can be commissioned easily and quickly.
Precondions
The V
/f characterisc control is only suitable for asynchronous motors.
If y
ou want to actuate a drive with a square-law V/f characterisc: Please always check
whether the corresponding drive is suitable for operaon with a square-law V/f character-
isc!
Se
t the motor data according to the informaon on the nameplate of the motor. 4Mot
or
data ^ 38
13.4.1 Required commissioning steps
1.
Check wiring b
y means of manual test modes. 4
Tesng the motor control ^ 299
2.
Acvate motor control type: 0x2C00 = "V/f characterisc control (VFC open loop) [6]".
3.
Set
liming factors for the V/f characterisc:
1.
0x2540:001, Ra
ted mains voltage
2.
0x2B01:001, Base voltage
3.
0x2B01:002, Base frequency
4.
Set and opmise current controller 4Curr
ent controller. ^ 265
Seng and opmising the current controller is only required if at least one of the following
funcons is acve:
V
oltage vector control 4
Acvate voltage vector control (Imin controller) ^ 241
DC braking 4DC braking ^ 249
Flying restart funcon4Flying r
estart circuit ^ 247
5.
Select a characterisc shape suitable for the applicaon 4Dene V/f characterisc shape.
^ 239
6.
Set voltage boost ^ 243
7.
Acvate voltage vector control (Imin controller) ^ 241
8.
Ima
x controller ^ 270
9.
Oponal4Se
t load adjustment ^ 244
10.
Oponal4Flying r
estart circuit ^ 247
11.
Oponal4Set slip compensaon ^ 244
12.
Oponal4Se
t oscillaon damping ^ 245
Conguring the motor control
V
/f characterisc control for asynchronous motor (VFC open loop)
Required commissioning steps
237