Parameter
Address Name / seng range / [default seng] Info
0x5850:001 Kommandos für Systembus EtherCAT-Master: Kommu-
nikaon neu starten
0 No acon/no error
1 Neustart
10 Busy
11 Cancelled
12 Faulted
16.2.2 Basic seng and opons
The content of this secon is currently being processed.
16.2.2.1 Synchronisaon with "distributed clocks" (DC)
The content of this secon is currently being processed.
Parameter
Address Name / seng range / [default seng] Info
0x10F8 Actual me stamp
R
ead only: x ns
The me informaon currently used by the inverter (the device me, so
to speak).
0x2580:001 Distributed Clocks : Real me status
Read only
Since its switch-on, the inverter has not yet received any real me infor-
maon from outside.
The inverter sll works with a me based on the me of the last switch-
o or the me stamp of the rmware.
0 Not adjusted Since its switch-on, the inverter has not yet received any real me infor-
maon from outside.
1 Adjusted once
2 Adjusted cyclically
0x2580:002 Distributed Clocks : First seng me
R
ead only: x ns
Display of the me when the inverter has received a real me informa-
on from outside for the for rst
me aer its switch-on.
In the "No real me informaon received yet", the value "0" is displayed.
0x2580:003 Distributed Clocks : Newest seng me
R
ead only: x ns
Display of the me when the inverter has most recently received a real
me
informaon from outside.
0x2580:004 Distributed Clocks : Current me
R
ead only: x ns
Display of the me
informaon currently used by the inverter (device
me).
16.2.2.2 Parameterising addional
funcons
Parameter
Address Name / seng range / [default seng] Info
0x2946:001 Speed limitaon: Upper speed limit
-479999.999776482 ... [0] ... 479999.999776482
rpm
Upper limit for the speed limitaon.
Seng is only eecve with the selecon "Upper speed limit [5]" in .
Entry via keypad and Lenze Tools is in rpm!
Via RPDO, the unit is vel. unit. and the scaling must be taken into
account.
± 480000 rpm = ±2 ^ 31 [n-unit]
0x2946:002 Speed limitaon: Lower speed limit
-479999.999776482 ... [0] ... 479999.999776482 rpm
Lower limit for speed limitaon.
Seng is only eecve with the selecon "Lower speed limit [5]" in .
Entry via keypad and Lenze Tools is in rpm!
Via RPDO, the unit is vel. unit. and the scaling must be taken into
account.
± 480000 rpm = ±2 ^ 31 [n-unit]
0x2DD5 Torque setpoint
Read only: x.xx Nm
Display of the current torque setpoint.